CATL lithium iron phosphate battery, stable and safe, cell, battery pack, system triple protection
Modular design, plug and play, global cloud platform & mobile APP access, open API
Support photovoltaic 200% superallocation, support and off-grid parallel function
Three-phase power adjustable, support optical storage of micro-grid (dry contact reserve)
| System parameters | Running parameters | ||
| Battery type | LFP (LifePO4) | Maximum charging/discharging current | 50A/80A |
| System weight | 54KG | Rated DC power | 4096W |
| Dimensions (W × H × D) | 540×490×240mm | Maximum charging/discharging power | 2825W/4096W |
| Protection class | IP65 | Operating temperature range | -10 to 50℃ Charging -10 to 50℃ discharge |
| Warranty | 5 years Product Warranty 10 years Performance Guarantee | Humidity | 0-95% (non-condensing cream) |
| Electrical parameters | BMS | ||
| Power capacity | 5.12kWh | Modules are connected | ≤8 |
| Available capacity | 4.5kWh | Capacity | 200 -800 Ah |
| Discharge depth (DOD) | 90% | Power loss | <2W |
| Rated voltage | 51.2V | Communication mode | CAN & RS485 |
| Dc circuit breaker | 125A | Monitoring parameters | System voltage, current, cell voltage, cell temperature, PCBA temperature detection |
| Operating voltage range | 44.8-56.5V | Certification | |
| Internal resistance | <20mΩ | Safety gauge (cell) | Pack:IEC/EN 62619;UN38.3 Cell:IEC/EN 62619;UN38.3;UL1973 |
| Cycle life | 10000 cycles | ||
| Input parameter (DC) | Efficiency | ||
| Maximum photovoltaic access capacity | 20kW | Maximum efficiency | 97.6% |
| Maximum DC voltage | 1100V | European efficiency | 97.0% |
| Starting voltage | 130V | Protection | |
| MPP voltage range | 140~1000V | Anti-island protection | Yes |
| Full load MPPT voltage range | 420~850V | Output overcurrent protection | Yes |
| Rated input voltage | 720V | DC reverse protection | Yes |
| MPPT Number | 2 | Series fault detection | Yes |
| Maximum number of MPPT access groups per channel | 1 | AC/Direct surge protection | DC Type II;AC Type III |
| The maximum input current of each MPPT | 15A | Insulation impedance detection | Yes |
| Maximum short circuit current of each MPPT | 20A | AC short circuit protection | Yes |
| Output parameters (AC) | General parameters | ||
| Rated AC output power | 10kW | size (width × height × thickness) | 540×980×240mm |
| Maximum AC apparent power | 11kVA | Weight | 42kg |
| Rated AC voltage | 400Vac, 3P+N+PE | Operating temperature range | -25℃~+60℃ (>45℃ derated) |
| Ac power grid frequency range | 50/60Hz | Noise (dB) | <25 |
| Rated output current | 14.5A | Cooling mode | Natural heat dissipation |
| Maximum output current | 16A | Maximum working altitude | 3000m (>2000m derated) |
Power factor (cosΦ) | 0.8 Lead -0.8 lag | Working humidity | 0~95% (no condensation) |
| Battery input | Protection class | IP65 | |
| Battery type | LFP (LiFePO4) | Circuit topology | Battery isolation |
| Rated battery voltage | 48V | Communication | RS485/CAN2.0/WIFI/4G |
| Charging voltage range | 40-60V | Display | LCD/APP |
| Maximum charging current | 200A | Certification & Standard | IEC/EN 62109-1&2;IEC/EN61000-6-1;IEC/EN61000-6-2; EN61000-6-3; IEC/EN61000-6-4;IEC/EN61000-3-11; EN61000-3-12;IEC60529;IEC 60068;IEC61683;IEC62116; IEC61727;EN50549-1; |
| Maximum discharge current | 200A | ||
| Battery capacity | 200-800Ah | ||
| Lithium battery charging strategy | Depends on BMS | ||
| Ac output (off-grid) | |||
Maximum output apparent power | 10kVA | ||
| Maximum output current | 16A | ||
| Rated output voltage | 400V | ||
| Rated output frequency | 50/60Hz(±2%) | ||
| Output voltage harmonics (@ linear load) | <3% (linear load) | ||